A vulnerability has been identified in SIMATIC Drive...
High severity
Unreviewed
Published
Feb 10, 2022
to the GitHub Advisory Database
•
Updated Apr 19, 2023
Description
Published by the National Vulnerability Database
Feb 9, 2022
Published to the GitHub Advisory Database
Feb 10, 2022
Last updated
Apr 19, 2023
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions), SIMATIC S7-PLCSIM Advanced (All versions), TIM 1531 IRC (incl. SIPLUS NET variants) (All versions >= V2.2). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packet over port 102/tcp. A restart of the affected device is needed to restore normal operations.
References